The Fire-Side Work and License Routing SOP

Purpose

A combination panel runs a burglar system and a fire system on one board, one power supply and one communicator. That means a tech who came to fix a door contact can take the house's smoke detection out of service by powering the panel down, and a tech without the fire license the jurisdiction requires can end up testing detectors the shop is not allowed to touch. When that goes wrong it is not a callback, it is a house with no fire signal to the station during work nobody recorded. This procedure catches the fire side at intake, routes it to a licensed tech, tells the station and the owner before anything is touched, tests to NFPA 72 in the edition the jurisdiction has adopted, and logs the impairment from its start to its verified end.

Scope

Covers any work on a combination fire and burglary panel, or on smoke, heat or CO devices connected to an alarm panel, where the work touches a fire device, fire wiring, or anything the fire side depends on: panel power, the battery, the communicator, the board. Residential and light commercial.

Does not cover what decides which work needs which license (see related: Combination Fire and Burglary Panels and the License Line), standalone household smoke alarm placement, or commercial fire alarm systems beyond the shop's license. Impairment notification for a commercial or multi-tenant building follows 'The Fire Alarm Impairment Notification SOP' in full; this procedure points to it at step 3.

Roles and responsibilities

Role Owns Hands off to
Office Flagging fire-side work at intake, matching a licensed tech, the impairment log Licensed tech, with the flag and the device list
Licensed fire tech Notifications, testing, restoring, the test record Office, with the record and the impairment end time
Burglary-only tech Burglary work that does not touch the fire side Licensed tech, if the job turns out to touch it
Central station Fire signals on test, confirming each one, restoring Licensed tech, by confirmation number
Owner or occupant Being told before work, the compensating measure Office, by acknowledgment

Procedure

  1. Flag fire-side work at intake. The office reads the account's zone list and marks the ticket "fire side" if any zone is a fire, heat, CO or supervisory type, or if the panel is a combination panel and the job could involve panel power, battery, board or communicator. Acceptance: the flag set or cleared, with the reason, before the job is assigned. Wrong looks like a "battery replacement" ticket on a combination panel left unflagged; the stop rule is any job that removes panel power is fire-side on a combination panel. Hazard: none, desk work.

  2. Confirm the tech holds the license the jurisdiction requires. Fire alarm licensing is set by the state, the city or both, and varies widely; some jurisdictions license fire alarm work separately from burglar alarm work, and some require a permit for changes. The office records, for the premises' jurisdiction, the license type the work needs and the assigned tech's license number and expiry. Acceptance: a matching, unexpired license on the ticket. Wrong looks like a burglary-only license for a job flagged fire side; the stop rule is the fire-side work is reassigned to a licensed tech or a licensed fire alarm contractor, and the burglary-only tech does only work that does not touch the fire side or panel power. Hazard: none, desk work.

  3. Notify the station and the owner before touching anything. The licensed tech calls the station, puts the account on test for all signals including fire, states which fire zones will be tested and the window, and records the confirmation number and operator ID (see related: How to Put an Alarm Account on Test and Take It Off). The owner or occupant is told that fire signals will not reach the fire department during the window and is given the compensating measure: household smoke alarms that are not on the panel stay in service, and occupants call 911 directly for any fire. Where the occupancy or the jurisdiction requires notifying the fire department or the AHJ, that call is made too, per 'The Fire Alarm Impairment Notification SOP'. Acceptance: confirmation number, owner acknowledgment, and any AHJ notification on the ticket, with times. Wrong looks like a station that puts only burglary zones on test; the stop rule is no fire device is tripped until fire signals are confirmed on test. Hazard: none, phone calls.

  4. Open the impairment log. Record start time, which devices and zones are out of service, the compensating measure, and the expected end. Acceptance: a log entry before the first device is touched. Wrong looks like a log opened after the panel is already down; the stop rule is the tech stops, opens it with the true start time, and writes why it is late. Hazard: none, paperwork.

  5. Do the work and test each fire device as NFPA 72 requires. Test to the inspection, testing and maintenance chapter of NFPA 72 (Chapter 14 in recent editions) in the edition the jurisdiction has adopted, using the test method the device's maker specifies: a listed aerosol or the maker's method for smoke detectors, the maker's heat source for restorable heat detectors (never an open flame), and the maker's test procedure for CO detectors. Acceptance: each device received at the station as a fire, CO or supervisory signal, as its type requires, under its own zone and description, and restored. Wrong looks like a device that does not alarm, or reports as a trouble or under a burglary zone type; the stop rule is the device is replaced or the zone corrected now, or the impairment stays open with a return time if the part is not on the truck. Hazard: detectors on ceilings are reached from a stepladder on level floor, not from furniture; aerosol is sprayed in short bursts away from the face; a panel with a 120 V branch circuit is opened only by a qualified person who proves it dead on a tester checked on a known live source before and after, per NFPA 70E Article 120 in the current edition, with work practices at 29 CFR 1910.333(b)(2), and otherwise by an electrician.

  6. Restore and prove normal. Restore panel power in the order the panel's manual gives, observing battery polarity. Acceptance: panel shows normal with no trouble, a final fire test signal and its restore confirmed by the station, the account off test with the operator ID recorded. Wrong looks like a ground-fault or battery trouble after restoring; the stop rule is the account stays on test and the impairment stays open until it clears. Hazard: re-applying power to a panel is done with hands clear of the board and terminals, and a detector that sounds on power-up is treated as a real alarm until the tech has looked at that room.

  7. Close the impairment and the record. Close the log with the end time, tell the owner that fire signals are reaching the station again, close any AHJ notification, and complete the test record in the form NFPA 72 and the AHJ require. Acceptance: impairment end time, owner told, record filed, and any required submission sent. Wrong looks like an impairment closed with a device still failed; the stop rule is the log stays open and the owner is told which device is out. Hazard: none, paperwork.

The record this produces

The ticket's fire-side flag and reason, the license match, notification times and confirmation numbers, the impairment log from start to end, the device-by-device test record with method and result, and any AHJ submission. The office keeps it with the account; the next licensed tech reads it before the next test; an AHJ or insurer asking what was out of service and for how long reads the impairment log.

A worked pass

A combination panel in a single-family house: 8 burglary zones, 3 smoke detectors on fire zone 9, a heat detector in the garage on fire zone 10, a CO detector on zone 11. Zones 9 to 11 are the fire side. Ticket: replace the panel battery.

Step 1. Flagged fire side: a battery change removes standby power from the fire zones.

Step 2 triggers its stop rule. The tech first assigned holds the burglar license only; this city licenses fire alarm work separately. Reassigned to a licensed tech with an unexpired fire license, number and expiry on the ticket.

Steps 3 and 4. Account on test for all zones, 2-hour window, 09:30. Owner told; compensating measure: the house's two standalone smoke alarms stay in service and the household calls 911 directly. No AHJ call is required for this occupancy here. Impairment opened 09:32, zones 9, 10 and 11.

Step 5 fails its acceptance. Battery replaced. Testing every fire-side device, which is the shop's rule after any power work on a combination panel, the three smoke detectors and the CO detector each reach the station correctly. The garage heat detector, a restorable type tested with the maker's heat tool, does not alarm after the maker's stated time. Stop rule taken: no replacement on the truck, so the impairment stays open for that zone only; the owner is told the garage has no heat detection reaching the station, and a return is booked for the next morning.

Steps 6 and 7. Panel normal, final fire test confirmed, account off test 10:50. The impairment log reads "zones 9 and 11 restored 10:50; zone 10 (garage heat) open, return booked." It closed the next day at 09:15 after the new detector passed.

References

  • NFPA 72, National Fire Alarm and Signaling Code, in the edition adopted by your jurisdiction (inspection, testing and maintenance chapter)
  • NFPA 70E Article 120, current edition, and 29 CFR 1910.333(b)(2), for any 120 V panel circuit
  • See related: The Fire Alarm Impairment Notification SOP
  • See related: Combination Fire and Burglary Panels and the License Line
  • See related: What a Fire Alarm Panel Is Actually Doing