Radon Mitigation Basics Reference
Why this reference exists
Radon is the leading cause of lung cancer in non-smokers + the second-leading cause overall. The EPA estimates 21,000 U.S. deaths/year. About 1 in 15 U.S. homes has radon above the 4 pCi/L action level. Mitigation systems sell at a healthy ticket and require specialized but learnable installation. Many HVAC + basement-finishing crews add radon mitigation as an adjacent service line. This reference is the working summary.
What radon is + where it comes from
Radon is a naturally-occurring radioactive gas from uranium decay in soil + rock. Colorless, odorless, tasteless. Released into the air everywhere; outdoor concentrations are low (~0.4 pCi/L average). Indoor air can accumulate radon when:
- Building sits on uranium-bearing geology (granite, shale, phosphate)
- Soil + rock around foundation is permeable
- House has lower air pressure than surrounding soil (most do, especially in winter)
- Foundation cracks + penetrations let radon in
Radon levels are not predictable by region only - adjacent homes can vary 10x. Testing is the only way to know.
EPA action level
- Below 2 pCi/L: low; no action needed
- 2-4 pCi/L: consider mitigation
- 4+ pCi/L: EPA recommends mitigation
- 10+ pCi/L: urgent mitigation; minimize occupancy in basement until fixed
- 20+ pCi/L: emergency; some authorities recommend immediate occupancy reduction
Real estate transactions in many states trigger mandatory disclosure + testing. Real estate testing is short-term (48 hours, charcoal canister). Long-term testing (3-12 months, alpha track detector) gives a more accurate seasonal average.
How mitigation works
The dominant residential mitigation: Active Soil Depressurization (ASD). A fan pulls air from below the slab + exhausts above the roof line. The slab + foundation become a sealed surface that air no longer migrates THROUGH.
Components:
- Suction point(s) under slab - typically PVC pipe penetrating slab
- Sealed sump pit (if present)
- Vertical riser pipe through interior or exterior of house
- Inline fan (Radonaway RP145, RP265; Festa Eagle, similar)
- Exit point above roofline OR away from windows + intakes
- Manometer (U-tube water column) showing suction; visible to customer
- Sealed cracks + penetrations in slab
Mitigation typically reduces radon 80-99%.
Site assessment
Step 1: Test for baseline radon
Long-term test (alpha track 3-12 months) OR short-term (charcoal 48 hours). Customer-paid; mitigator provides referrals or testing.
Step 2: Inspect foundation
- Slab on grade (basement floor)
- Crawl space (open dirt floor or partial slab)
- Sump pit (often the suction point)
- Cracks + penetrations (utility pipes, water lines, expansion joints)
Step 3: Plan suction points
- 1 point per 2,000 sq ft of slab typical
- More if slab is interrupted by foundation walls, partitions, additions
- Sub-slab communication test: drill small hole, run vacuum, measure pressure at distant point - if pressure pulls, communication is good
Step 4: Plan riser route
- Interior route: through unfinished basement up through utility chase or closet
- Exterior route: PVC pipe up exterior wall (faster install, visible)
- Exit above roofline; 10+ ft from windows + intakes; 2+ ft above eave
Step 5: Plan electrical
- 120V dedicated circuit for fan
- Switch in conditioned space for service shutoff
- Manometer accessible
Standard install procedure
Step 1: Cut slab + create suction pit
- 6" diameter core-drill or saw-cut slab
- Excavate 18-24" of gravel + dirt below to create suction pit
- Verify suction communication (test with vacuum + manometer)
Step 2: Install suction pipe
- 3" or 4" PVC pipe through slab to suction pit
- Seal slab around pipe with polyurethane sealant
- Reduce to 3" for riser run (most fans 3")
Step 3: Run riser pipe
- PVC SDR-21 or SCH-40 pipe + fittings
- Route to exterior or up through interior
- Insulate runs in unconditioned space (prevents winter condensation)
Step 4: Install fan
- Mount in unconditioned space (attic OR exterior wall outside livable space)
- Boot connections
- 120V wire to switch + breaker
- Manometer installed visible in basement
Step 5: Exit pipe
- Run pipe above roofline (typically through gable end + up, or vertical through roof flashing)
- 10+ ft from windows + intakes
- 2+ ft above eave
- Bird screen at exit
Step 6: Seal + commission
- Seal slab cracks + penetrations with polyurethane sealant
- Seal sump pit (if present) with a sealed cover allowing pump access
- Energize fan
- Verify manometer reading (typically 0.5-1.5 in WC of water column = good)
- Customer briefing
Step 7: Re-test after install
Run a post-mitigation radon test (3-7 days, short-term). Provide results to customer. EPA + state programs typically require this.
Acceptance criteria
- Post-mitigation radon < 2 pCi/L (best) or below action level
- Manometer reading within design range
- All slab cracks + penetrations sealed
- Fan operating + audible
- Customer signed work order
- Post-mitigation test results delivered
Common pitfalls
- Wrong fan size: too small = no suction, too big = wasted energy + noise
- Bad exit location: 5 ft from window = radon re-entry
- Unsealed slab cracks: fan pulls air from cracks (short-circuit) rather than soil
- Sump uncovered: huge air leak path
- No manometer: customer can't see whether fan is running
- Pipe through conditioned space without insulation: condensation drips
- Fan inside living space: noise complaint + maintenance access
- No post-mitigation test: customer + agency wants verification
Crawl space variant
Open dirt-floor crawl spaces use a different approach:
- Lay 6-mil polyethylene over dirt
- Seal seams + edges to foundation walls
- Penetrate with suction pipe under the sheeting
- Same fan + riser system as ASD
Encapsulating a crawl space is often combined with radon mitigation since the membrane is needed for both. Higher ticket: combined.
Radon-resistant new construction (RRNC)
For new builds, designing radon resistance during construction:
- Gravel layer below slab (passive collection medium)
- Capped passive vent pipe from gravel up through roof
- Sealed all slab penetrations
- Polyethylene under slab
- Easy fan-activation if later test shows high
Adds modest cost during construction; saves a multiple of that if the house later tests high and needs a retrofit.
State + utility incentives
Some states + utilities subsidize radon mitigation:
- Maine, Minnesota, Pennsylvania, Iowa have state programs
- Utility energy efficiency programs sometimes include if ERV/HRV bundled
- Health-department programs for low-income households
Verify locally; where a program exists, the rebate usually offsets a meaningful share of the install, and it is often tied to using a certified mitigator.
Certifications
Radon work is credentialed work in most of the country, and measurement and mitigation are separate credentials. A tech certified to test is not automatically certified to install, and several states enforce that split.
The two national programs:
- NRPP (National Radon Proficiency Program), administered by AARST.
- NRSB (National Radon Safety Board).
Both issue individual certifications, both require an approved course plus a proctored exam, and both require continuing education and periodic renewal. States that license radon work generally accept one or both, but check which one your state names before you pay for a course.
What the credential actually requires you to do: work to the ANSI/AARST standards, use calibrated and cross-checked measurement devices, follow device-specific protocols including the closed-house conditions before and during a short-term test, and keep records. Measurement certification also carries proficiency requirements: duplicate tests, blanks, and spikes at defined intervals, which is how the program verifies your numbers are real.
Licensing is a separate question from certification. Many states license radon contractors on top of the national credential, some require registration of each installed system with the state, and real estate transactions in disclosure states frequently require the tester to be certified and independent of the mitigator. Check your state radon program directly, not a course provider's summary.
Do not test your own mitigation and call it verification where the state or the transaction requires independence. Even where it is permitted, an independent post-mitigation test protects you from the accusation that the number was convenient.
Practical path in: measurement certification first, since it is cheaper and gets you diagnosing and quoting; mitigation certification next, once you have installed under someone certified. Carry liability coverage that names radon work specifically, because a general contractor policy may exclude it.
References
- EPA Citizen's Guide to Radon
- EPA Radon Mitigation Standards (ANSI-AARST)
- NRPP + NRSB Certification + Training
- State radon program contacts
- Manuall internal: Indoor Air Quality - ERV and HRV Reference